DIN rail mountable 12V DC 420mA output power supply, suitable for industrial control equipment.
Universal input 90 to 264V AC with short circuit protection and internal input filter.
Low profile for building automation.
Suitable for use with the 5500CN2 - C-Bus Network Interface V2.
- Universal mains input & 120-370V DC
- Regulated, single outputs
- 10W AC/DC DIN rail converters
- -40°C to +71°C operation
- Nominal Current 420mA
- Low profile DIN rail mount profile (56mm)
Input |
Input Internal Fuse: | T|A /250V AC |
Rated Input Voltage: | 100-240V AC |
AC Voltage Range: | 90-264V AC |
DC Voltage Range: | 120-375V DC |
Frequency: | 47-63Hz |
Rated Input Current: | 300mA | |
Inrush Current (115V AC/230V AC): | <15A/<30A | |
Efficiency(Typ): | 78% | |
Power Factor Correction: | Meets EN6100-3-2 class A | |
|
Output |
Turn On Time: | <1000ms after AC is applied to input at full resistive load |
Turn On Time-with capacitive load: | <1500ms W /3500 µF |
Rise Time: | <150ms full resistive load |
Rise Time-with capacitive load: | <500ms W /3500 µF |
Over Voltage Protection: | 15-16.5V DC |
Line Regulation: | ±1.0% |
Load Regulation: | ±1.0% |
Temperature Coefficient: | ±0.03%/°C |
Initial Voltage Setting: | 12V±1% |
DC ON Indicate(Green LED): | 9-10.8V |
DC LOW Indicate(Red LED): | 9-10.8V< |
Ripple & Noise(BW=20MHz): | <50mVp-p |
Nominal Current: | 420mA |
Rated Overload Protection: | 110%-165% |
Output Short Circuit: | Fold forward |
Holdup Time(230Vac): | >30ms |
Fall Time: | <150ms from 95% to 10% rated voltage @ full load |
|
General |
Isolation Voltage: | 3000V AC/4242V DC |
Isolation Resistance: | 100M Ohm |
Cooling: | Free Air Convection |
Temperature Storage: | -40 to +85°C |
Temperature Operation: | -40 to +71°C |
Derating: | 2.5%/°C from 61°C to 71°C |
Humidity: | 20-95% RH |
Case Material: | Plastic |
Max Required Free Space: | 25mm on all sides |
Dimensions: | 91x18x56.5mm(3.58x0.71x2.22in) |
Weight: | 65g |
|
Approvals and Standards |
UL/cUL: | UL508 Listed, UK1310 Class 2 Power, UK60950-1 Registered, ISA 12.12.01 |
TUV: | EN 60950-1 |
CE: | EN 6100-6-3, EN 55022, Class B, EN 61000-3-2, EB61000-3-3, EN6100-6-2, EN55024, EN6100-4-2, -3, -4, -5, -6, -8, -11, EN61204-3 |