The C-Bus 4 Channel General Input Units are DIN rail mount units designed to measure digital, voltage. current loop and thermistor inputs and generate messages to the C-Bus network.
The unit is designed to broadcast the actual measured value to the C-Bus network, which in turn may be displayed on other C-Bus devices such as the touch screen, C-Gate or C-Lution. In addition, the unit may trigger a Group Address as a function of the input level. up to eight trigger points may be assigned to a single input channel.
The general input unit is designed to interface to third party products, such as light level sensors, temperature sensors, power, frequency, moisture, rate sensors and others. In this way, the general input may be used to extend the functionality of the C-Bus and its ability to integrete with other systems such as HVAC and power monitoring systems. The general input also generates 24VDC to power the external sensors.
The general input units are available as passive models only, hence do not source current to the C-Bus network.
- Provides 4 channels of input with a range of third party sensor products.
- Capable of threshold switching or broadcasting value onto the network.
- Programmable via the C-Bus configuration software.
- Programmed variables are stored in non-volatile memory and are retained in case of loss of mains or C-Bus power.
- Designed to fit onto standard 35mm top hat DIN rail, measures just 8M in size.
- Designed to fit into standard electrical switchboards.
- CE compliant.
Supply Voltage | 24V AC/DC +/- 10% @500mA, power pack not included |
Supply Frequency | 50/60Hz |
C-Bus Supply Voltage | 15-36VDC @ 18mA |
Auxiliary Output | 24VDC@250mA |
Voltage Inputs | 0 - 1V ,0 - 5V, 0-10V and 0 - 20V |
Current Inputs | 0 - 20mA and 4 - 20mA |
Impedance Inputs | 0 - 500Ω, 0 - 1kΩ and 0 - 3kΩ |
Digital Inputs | Yes |
Broadcast Rate | 2 to 1,024 seconds |
Maximum Number of Units on a Single C-Bus Network | 10 |
Status Indicators | Unit and C-Bus |
A/D Conversion | 8 bit |
Accuracy | 0.5% |
Warm Up Time | 5 seconds |
Network Clock | Software selectable |
Network Burden | Software selectable |
C-Bus Termination | 2x RJ45 Socket |
Load Termination | 2x 1.5mm² or 1x 2.5mm² |
Operating Temperature | 0°C to 45°C |
Operating Humidity | 0 - 95% RH, non condensing |